Filter Fan Unit LIGHT

  • Advanced Technology Facilities
FFU LIGHT (Grid size 1200x1200 mm)
FFU LIGHT (Grid size 1200x1200 mm)
Air circulation in cleanrooms with turbulent flow

The FFU LIGHT is a reasonably priced FFU

for the use in turbulent cleanroom areas with low requirements regarding noise level. Depending on the configuration of the filter coverage and of the filter classes, cleanroom classes of ISO 5.0 to ISO 8.0 according DIN EN ISO 14644-1 can be reached.

The FFU LIGHT is available with a alternating current motor or a EC-Motor.

The product FFU LIGHT EC is protected by patent.

  • Cleanroom classes 5 to 8 according to ISO 14644-1
  • Cleanroom classes D, C, B according to EU GMP guideline
  • For cleanrooms with low sound level requirements
  • Low power consumption

Technical Data

Performance Parameters
Typ Value
Grid size length: 1,200 mm | width: 1,200 mm
Housing length 1,132 mm
Housing width 1,132 mm
Housing height 350 mm
Weight 21 kg
Voltage between 200 V and 277 V
Phase 1 ~
Frequency 50 Hz / 60 Hz
Rated current between 1.8 A and 1.3 A
Rated capacity 370 W
Number of revolutions min.: 300 1/min | max.: 1,304 1/min
Operating temperature min.: 0 °C | max.: 40 °C
Flow velocity 0.45 m/s
Air volume flow 2,330 m³/h
Differential pressure 120 Pa
Power consumption 186 W
Sound power level pressure side: 69 dB (A)
Clean room sound pressure level 25 % occupancy: 68 dB (A)
Clean room sound pressure level 100 % occupancy: 75 dB (A)
External pressure difference max.: 235 Pa
Engineer Standards
  • DIN EN ISO 14644-1

Constructive Design

The unit consists essentially of the housing, the HEPA filter cell and the compact fan unit with impeller and motor with inlet nozzle.

The following additional accessories are available:

  • Prefilter for coarse particle filtration
  • AMC-filter for filtration of gaseous contaminants
  • Cooling coil/heating coil
  • Air diffusor (perforated plate diffusor, swirl outlet)

If necessary filter cell classes H13 to U17 can be used.

The FFU fans have sufficient reserve capacity to overcome any additional pressure loss due to e.g. raised floor, return air ducts, prefilter or cooling/heating coils.
The FFU LIGHT AC is driven by a special developed single phase external rotor AC motor with internally wired thermal contacts for overload protection.
The FFU LIGHT EC is driven by an electronically commutated external rotor motor.

Accessories

  • Particle Filter (All Filters as Filter with dry sealant. Filters with fluid sealant are available upon request.)
  • AMC Filter for filtration of gaseous contaminants
  • Prefilter for coarse particle filtration (Prefilter incl. Filterframing made in Aluminium)
  • Diffusors for air distribution (Diffusor Aluminium anodized and Aluminium powder coated)
  • Installation Frame for third Party Ceiling Systems (Filter Installation Frame Aluminium anodized and Aluminium powder coated)
  • Cooling Coil
  • Aerosol Measurement Connector

Properties

  • Cleanroom classes 5 to 8 according to ISO 14644-1
  • Cleanroom classes D, C, B according to EU GMP guideline
  • For cleanrooms with low sound level requirements
  • Low power consumption
  • Low sound pressure level
  • Low maintenance effort
  • For cleanrooms with low overall height
  • Minimized installation effort due to plug & play cable system
  • Easy device installation from below (cleanroom side) with bearing rails
  • Optional installation from top (plenum side)
  • Best price-performance ratio
  • With connection for particle and differential pressure measurement
  • FFU sizes fit in ceiling grid size (1200 mm × 1200 mm, 1200 mm × 900 mm, 1200 mm × 600 mm)
  • Low weight
  • Easy operation
  • Applicable for individual workstations or entire cleanroom facilities
  • Aluminium housing (standard)
  • HEPA / ULPA filter classes H13 to U17
  • Installed radial fan balancing grade G= 2,5 according to DIN ISO 1940-1, motor with internal wired thermal contact

Suitable Products

Control terminal
Control Terminal

The Control Terminal is used to manage, monitor and display information of networks up to 199 fan units.

more
iTAC
CRiSxt

The CRiSxt control system (including hardware and software) is used to manage and monitor networks of up to 70,000 units via LonWorks.

more