Filter Fan Unit PIFF COMPACT

  • 先进技术设施
  • 生物制药&生命科学
PIFF-COMPACT module without air grill and installation frame, incl. make-up/exhaust air connection (optional) (Grid size 1200x1200 mm)
Typical room air velocity situation with turbulent mixed air generated by a PIFF-COMPACT (example)
Supply air grill with return air inlet, view from below

The PIFF-COMPACT

is a Plenum Integrated Filter Fan which usually works with recirculation air. Thereby no return or supply air ducts are needed on the ceiling which leads to a considerable reduction of installation effort as well as space-saving.

Depending on the coverage of the clean room ceiling, the classes 5.0 to 8.0 according to DIN EN ISO 14644-1 as well as B, C and D according to EC Guide “GMP” can be achieved. The PIFF-COMPACT is installed into the existing ceiling grid by an installation frame.

  • Easy device installation
  • Integrated air cooling coil (without valve or thermostat, water connection 3/4” female thread)
  • Compact recirculating air cooling device
  • Self-contained return air unit

Felix Hirt
Head of Sales

Phone: +49 711 8804-2597

Mobil: +49 1749407118

felix.hirt@exyte.net

Mohandoss Manikant
Head of Sales – Corporate Clients, Business Area Exyte Technology

Mobil: +001 208 841-7611

manikant.mohandoss@exyte.net

Technical Data

Performance Parameters
Typ Value
Grid size length: 1,200 mm | width: 1,200 mm
Housing length 1,100 mm
Housing width 1,100 mm
Housing height 590 mm
Weight 70 kg
Voltage between 200 V and 277 V
Phase 1 ~
Frequency 50 Hz / 60 Hz
Rated current between 1.8 A and 1.3 A
Air volume flow 1,500 m³/h
Rated capacity 280 W
Sound power level 68 dB (A)
Clean room sound pressure level 25 % occupancy: 68 dB (A)
Separation efficiency in MPPS 100 %
Pressure drop 126 Pa
Cooling capacity 2.6 kW
Media volume flow 0.4 m³/h
Water temperature inlet: 14 °C
Water temperature outlet: 20 °C
Pressure drop waterside: 12.7 kPa
Air temperature inlet: 23 °C
Air temperature outlet: 18 °C
Pressure drop airside: 42 Pa
Engineer Standards
  • DIN EN ISO 14644-1

Constructive Design

The PIFF-COMPACT consists of an outer housing with make-up air connection and exhaust air connection together with the internal components HEPA filter cell with fan motor unit in a common internal housing and a cooling coil. As an option, a prefilter can be installed. The supply with fresh air and the collection of exhaust or return air is implemented by a specially designed air grill, which is located on top of the ceiling installation frame of the PIFF-COMPACT. The power and network connectors as well as the cooling water connections (supply /return) are located at the side of the unit. The control valve for the cooling coil is to be provided for a single or a group of PIFF-COMPACT (by others).

The fan draws air from the room via the return air intake in the outlet grill and channels the air through an optional prefilter to the cooling coil. The chilled air-flows through the HEPA filter and is blown with high turbulence into the cleanroom via the outlet air grill. This design prevents a short-cut between supply air and return air. The distribution elements of the outlet air grill are arranged in a special design to ensure a homogenous air distribution to all sides.

Accessories

  • Ceiling installation adapter for third party ceiling systems
  • Connection pieces
  • Prefilter
  • Aerosol inlet-/measurement connector

Properties

  • Easy device installation
  • Integrated air cooling coil (without valve or thermostat, water connection 3/4” female thread)
  • Compact recirculating air cooling device
  • Self-contained return air unit
  • Integrated prefilter
  • Plenum integrated in the device
  • Low sound power level
  • Easy retrofitting (increase of the recirculating air volume or cleanroom class)
  • No mixture of recirculation air from different production rooms
  • Low operating costs
  • Significant energy saving compared to the conventional ventilation concept (central recirculation device)
  • Optional makeup air and exhaust air connection
  • Low sound pressure level
  • Complete and compact plug & play unit
  • Cleanroom classes 5 to 8 according to ISO 14644-1
  • Easy device installation from below (cleanroom side) with bearing rails
  • Minimized installation effort due to plug & play cable system
  • Material/surface: aluminium untreated | steel powder coated | aluminium powder coated | stainless steel
  • Low maintenance effort
  • Easy operation
  • Cleanroom classes D, C, B according to EU GMP guideline
  • Low power consumption
  • Easy installation with ceiling installation frames and intermediate profiles for an optimal unit integration into the cleanroom ceiling system
  • Connections for particle and/or differential pressure measurements at the HEPA filter
  • Flexible in that way that the unit can be easily relocate

Suitable Products

Control terminal
Control Terminal

The Control Terminal is used to manage, monitor and display information of networks up to 199 fan units.

更多
iTAC
CRiSxt

The CRiSxt control system (including hardware and software) is used to manage and monitor networks of up to 70,000 units via LonWorks.

更多